Steel Truss

Installation & Design Considerations

  • FOAMULAR® insulation installed over the bottom chords of steel truss framing reduces heat loss through the framing.
  • Use, large head, screw type drywall fasteners to secure 1” thick, (typical maximum) foam insulation in position.
  • Attach drywall over the foam insulation. Use traditional drywall fasteners to secure drywall to the truss bottom chord.
  • Foam insulation must be covered on the attic side with an ignition barrier.
  • Install full width unfaced Thermal Batts of sufficient thickness to meet energy code requirements.
  • Maintain a minimum 1” ventilation passage way at the eaves with vents. Where necessary use Owens Corning Raft-R-Mate® vent baffles to assure proper clearance.
  • Attic must not be used as a return air plenum. Provide attic ventilation to meet code requirements.
  • Polystyrene insulation must be separated from the building interior with a code approved thermal barrier, typically 1/2” drywall.
  • The need for a vapor retarder should be determined by the designer based on local conditions. FOAMULAR® 150 has a perm rating less than 1.1.
  • Compliance with local code requirements must be verified.
  • Architect must supply detailed drawings to meet project and building code requirements.